82
will skip to normal operation interface if the MPPT scanning succeeds
or remain on the MPPT Scan menu interface if the scanning fails.
The factory default setting for "MPPTScan" is set to Enabled yet can
also be set to Disabled. When the MPPT scan function is enabled, the
default scan period is every 60 minutes. The inverter will scan the
maximum power point in the MPPT range, according to the following
conditions:
① While in Parallel mode, the total input power is lower than 90% of the
active power.
② While in Independent mode (3 MPPTs), the input power must be lower
than 75% of the rated power for each MPPT tracker.
Once this MPPT scan function is activated on the LCD, it will search
the maximum power point at a voltage step of 5V in the MPPT range
for the full load and retrieve the maximum power point.