Curtis 1243GEN2 Manual
38
3 — PROGRAMMABLE PARAMETERS:
Field Parameters
POT LOW FAULT
The pot low fault parameter allows the controllers pot low fault detection to
be disabled. This is useful when single-wire, ground (B-) referenced voltage
throttle inputs are used. Setting the pot low fault parameter to Off disables the
fault detection at the pot low input (Pin 7). It is recommended that the pot low
fault parameter be set to On in any application where a resistive throttle is used.
This will provide the most comprehensive throttle fault detection and provide
the safest possible vehicle operation.
Note: The programmers display name for the pot low fault is Throttle
Wiper Lo.
FIELD MIN
The minimum field current limit parameter denes the minimum allowed
eld current, thus determining the vehicles maximum speed. Field Min can be
adjusted from 1.6 amps up to the lowest programmed M1M4 Restraint value.
The Field Min parameter is tuned as part of the vehicle performance
adjustment process (Section 5).
FIELD MAX
The maximum field current limit parameter denes the maximum allowed
eld current. The maximum eld current limit setting determines the vehicles
maximum torque and the maximum power that the eld winding will have to
dissipate. Field Max can be adjusted from the programmed Field Min value up
to the controllers full rated eld current. (The full rated eld current depends
on the controller model; see specications in Table D-1).
The Field Max parameter is tuned as part of the vehicle performance
adjustment process (Section 5).
FLD MAP START
The field map start parameter denes the armature current at which the eld
map starts to increase from the programmed Field Min value. This parameter
is adjustable from 25 amps up to the full rated armature current value. (The full
rated armature current depends on the controller model; see specications in
Table D-1).
The eld map start parameter is used to equalize the vehicles maximum
speed when loaded and unloaded. Increasing the eld map start parameter
value will increase the maximum load weight that the vehicle can carry while
maintaining maximum speed on a level surface.
The eld map start parameter is tuned as part of the vehicle performance
adjustment process (Section 5).
Field Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Curtis Instruments MultiMode 1243 Generation 2 and is the answer not in the manual?

Curtis Instruments MultiMode 1243 Generation 2 Specifications

General IconGeneral
BrandCurtis Instruments
ModelMultiMode 1243 Generation 2
CategoryController
LanguageEnglish

Related product manuals