9 | Electrical installation
Installer reference guide
110
ERGA04~08EAV3(A) + EHVZ04+08S18+23EA6V+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
5 Fix the cable with cable ties to the cable tie mountings.
NOTICE
Make sure to select and install the safety thermostat for the additional zone
according to the applicable legislation.
In any case, to prevent unnecessary tripping of the safety thermostat, we
recommend the following:
▪ The safety thermostat is automatically resettable.
▪ The safety thermostat has a maximum temperature variation rate of 2°C/min.
▪ There is a minimum distance of 2 m between the safety thermostat and the
3‑way valve.
INFORMATION
ALWAYS configure the safety thermostat for the additional zone after it is installed.
Without configuration, the indoor unit will ignore the safety thermostat contact.
INFORMATION
The preferential kWh rate power supply contact is connected to the same terminals
(X5M/13+14) as the safety thermostat for the additional zone. It is only possible for
the system to have EITHER preferential kWh rate power supply OR a safety
thermostat for the additional zone.
9.3.10 To connect a Smart Grid
This topic describes 2 possible ways to connect the outdoor unit to a Smart Grid:
▪ In case of low voltage Smart Grid contacts