10 | Configuration
Installer reference guide
153
ERGA04~08EAV3(A) + EHVZ04+08S18+23EA6V+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
10.5.5 Space heating
Overview
The following items are listed in the submenu:
Space heating/cooling
Tank
Additional zone
Main zone
User settings
[4] Space heating/cooling
[4.1] Operation mode
[4.2] Operation mode schedule
[4.3] Operation range
[4.4] Number of zones
[4.5] Pump operation mode
[4.6] Unit type
[4.7] Pump limitation
[4.8] Pump limitation
[4.9] Pump outside range
[4.A] Increase around 0°C
[4.B] Overshoot
[4.C] Antifrost
About space operation modes
This unit is a heating only model. The system can heat up a space, but NOT cool
down a space.
Operation range
Depending on the average outdoor temperature, the operation of the unit in space
heating is prohibited.
# Code Description
[4.3.1] [4-02] Space heating off temperature: When
the averaged outdoor temperature rises above
this value, space heating is turned off.
▪ 14°C~35°C
Number of zones
The system can supply leaving water to up to 2 water temperature zones. During
configuration, the number of water zones must be set.
# Code Description
[4.4] [7‑02] ▪ 0: Single zone
Only one leaving water temperature zone:
a Main LWT zone