Installer reference guide
223
ERGA04~08EAV3(A) + EHVZ04+08S18+23EA6V+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
3 Carry out the forced cooling operation. See "15.3 To start and stop forced
cooling"[4223].
4 After 5 to 10minutes (after only 1 or 2minutes in case of very low ambient
temperatures (<−10°C)), close the liquid stop valve with a hexagonal wrench.
5 Check on the manifold if the vacuum is reached.
6 After 2-3minutes, close the gas stop valve and stop forced cooling operation.
a
c
b
d
d
e
a Liquid stop valve
b Closing direction
c Hexagonal wrench
d Valve lid
e Gas stop valve
15.3 To start and stop forced cooling
1 Turn OFF the power.
2 Remove the switch box cover.
3 Remove the service PCB cover.
1 2 3
L N
L N PWR
HEAT
COOL
4
3
2
1
2
1
E
D
C
B
A
A
1
2
3
4
5
SW1
SW3
SW2
SW5
SW6
SW4
S501
S502
S2
4 Set DIP switches SW5 and SW6 to OFF.
5 Set DIP switch SW2 to COOL.
6 Reattach the service PCB cover.
7 Turn the power back ON. Proceed with the next step within 3 minutes after
restarting.
8 To start forced cooling, press the forced cooling operation switch SW1.
9 To stop forced cooling, press the forced cooling operation switch SW1 again.