6 | Application guidelines
Installer reference guide
32
ERGA04~08EAV3(A) + EHVZ04+08S18+23EA6V+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
2 (Room thermostat): Unit operation
is decided based on the ambient
temperature of the user interface.
Note:
Main room = user interface used as
room thermostat functionality
Other rooms = external room
thermostat functionality
Number of water temperature zones:
#: [4.4]
Code: [7-02]
1 (Dual zone): Main + additional
In case of heatpump convectors:
External room thermostat for the
additional zone:
#: [3.A]
Code: [C-06]
1 (1 contact): When the used
external room thermostat or heatpump
convector can only send a thermo ON/
OFF condition.
Shut-off valve output Set to follow the thermo demand of the
main zone.
Benefits
Comfort. The smart room thermostat functionality can decrease or increase the
desired leaving water temperature based on the actual room temperature
(modulation).
Efficiency.
- Depending on the demand, the indoor unit supplies different leaving water
temperature matching the design temperature of the different heat emitters.
- Underfloor heating has the best performance with the heat pump system.
6.3 Setting up the domestic hot water tank
6.3.1 System layout – Integrated DHW tank
A Domestic hot water
a Cold water IN
b Hot water OUT