13 | Maintenance and service
Installer reference guide
205
ERGA04~08EAV3(A) + EHVZ04+08S18+23EA6V+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
13.3 Yearly maintenance
13.3.1 Yearly maintenance outdoor unit: overview
Check the following at least once a year:
Heat exchanger
13.3.2 Yearly maintenance outdoor unit: instructions
Heat exchanger
The heat exchanger of the outdoor unit can get blocked up due to dust, dirt,
leaves, etc. It is recommended to clean the heat exchanger yearly. A blocked heat
exchanger can lead to too low pressure or too high pressure leading to worse
performance.
13.3.3 Yearly maintenance indoor unit: overview
Water pressure
Magnetic filter/dirt separator
Water pressure relief valve
Relief valve hose
Pressure relief valve of the domestic hot water tank
Switch box
Descaling
Chemical disinfection
13.3.4 Yearly maintenance indoor unit: instructions
Water pressure
Keep water pressure above 1bar. If it is lower, add water.
Magnetic filter/dirt separator
b
a
c
d
a Screw connection
b Magnetic sleeve
c Drain valve
d Drain cap
The yearly maintenance of the magnetic filter/dirt separator consists of:
Checking if both parts of the magnetic filter/dirt separator are still screwed
tight (a).
Emptying the dirt separator as follows:
1 Take off the magnetic sleeve (b).