8 | Piping installation
Installer reference guide
71
ERGA04~08EAV3(A) + EHVZ04+08S18+23EA6V+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
The default pre-pressure of the expansion vessel is 1 bar. When it is required to
change the pre-pressure, take following guidelines into account:
Only use dry nitrogen to set the expansion vessel pre-pressure.
Inappropriate setting of the expansion vessel pre-pressure will lead to
malfunction of the system.
Changing the pre-pressure of the expansion vessel should be done by releasing or
increasing nitrogen pressure through the Schrader valve of the expansion vessel.
a
a Schrader valve
8.2.5 To check the water volume: Examples
Example 1
The indoor unit is installed 5m below the highest point in the water circuit. The
total water volume in the water circuit is 100l.
No actions or adjustments are required.
Example 2
The indoor unit is installed at the highest point in the water circuit. The total water
volume in the water circuit is 250l.
Actions:
Because the total water volume (250l) is more than the default water volume
(200l), the pre-pressure must be decreased.
The required pre-pressure is:
Pg = (0.3+(H/10))bar = (0.3+(0/10))bar = 0.3bar
The corresponding maximum water volume at 0.3bar is 290l. (See the graph in
"Maximum water volume"[469]).
Because 250 l is lower than 290 l, the expansion vessel is appropriate for the
installation.