10 | Configuration
Installer reference guide
140
ERGA04~08EAV3(A) + EHVZ04+08S18+23EA6V+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
# Code Description
[2.1] N/A Schedule:
▪ 0: No
▪ 1: Yes
Heating schedule
Define a heating temperature schedule for the main zone via [2.2] Heating
schedule.
See "10.3.7Schedule screen: Example"[4126].
Setpoint mode
In Fixed mode, the desired leaving water temperature does NOT depend on the
outdoor ambient temperature.
In Weather dependent mode, the desired leaving water temperature depends
on the outdoor ambient temperature.
# Code Description
[2.4] N/A Setpoint mode
▪ 0: Fixed
▪ 2: Weather dependent
When weather dependent operation is active, low outdoor temperatures will result
in warmer water and vice versa. During weather dependent operation, the user has
the possibility to shift the water temperature up or down by a maximum of 10°C.
Heating WD curve
Set weather-dependent heating for the main zone (if [2.4]=1 or 2):