10 | Configuration
Installer reference guide
150
ERGA04~08EAV3(A) + EHVZ04+08S18+23EA6V+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
# Code Description
[3.5] [0-00]
[0-01]
[0-02]
[0-03]
Set weather-dependent heating:
[0-00]
[0-01]
T
a
T
t
[0-03] [0-02]
T
t
: Target leaving water temperature
(additional zone)
T
a
: Outdoor temperature
[0-03]: Low outdoor ambient temperature.
40°C~+5°C
[0-02]: High outdoor ambient temperature.
10°C~25°C
[0-01]: Desired leaving water temperature
when the outdoor temperature equals or drops
below the low ambient temperature.
[9‑05]°C~[9‑06]°C
Note: This value should be higher than [0‑00]
as for low outdoor temperatures warmer water
is required.
[0-00]: Desired leaving water temperature
when the outdoor temperature equals or rises
above the high ambient temperature.
[9‑05]~min(45, [9‑06])°C
Note: This value should be lower than [0‑01] as
for high outdoor temperatures less warm water
is required.
Cooling WD curve
Set weather-dependent cooling for the additional zone (if [3.4]=2):