9 | Electrical installation
Installer reference guide
97
ERGA04~08EAV3(A) + EHVZ04+08S18+23EA6V+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
Item Description
Human Comfort Interface See:
▪ Installation and operation manual of the
Human Comfort Interface
▪ Addendum book for optional equipment
Wires: 2×(0.75~1.25mm²)
Maximum length: 500m
[2.9] Control
[1.6] Room sensor offset
WLAN adapter module See:
▪ Installation manual of the WLAN adapter
module
▪ Addendum book for optional equipment
Use the cable delivered with the WLAN
adapter module.
[D] Wireless gateway
LAN adapter See:
▪ Installation manual of the LAN adapter
▪ Addendum book for optional equipment
Wires: 2×(0.75~1.25mm²). Must be
sheathed.
Maximum length: 200m
See below ("LAN adapter – System
requirements").
LAN adapter – System requirements
The requirements posed on the system depend on the LAN adapter application/
system layout (app control, or Smart Grid application).
App control:
Smart Grid application:
Item Requirement
LAN adapter software It is recommended to ALWAYS keep the LAN adapter
software up-to-date.
Unit control method On the user interface, make sure to set [2.9]=2
(Control = Room thermostat)
Domestic hot water
settings
To allow for energy buffering in the domestic hot
water tank, on the user interface, make sure to set
[9.2.1]=4 (Domestic hot water = Integrated).
Power consumption
control settings
On the user interface, make sure to set:
▪ [9.9.1]=1 (Power consumption control =
Continuous)
▪ [9.9.2]=1 (Type = kW)