EasyManua.ls Logo

Daikin Altherma ERGA04E V3 Series - Page 68

Daikin Altherma ERGA04E V3 Series
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 | Unit installation
Installer reference guide
68
ERGA04~08E + EHVH04+08SU18+23E
Daikin Altherma 3 R F
4P629090-1C – 2022.08
Input from installer:
Total refrigerant charge (m
c
) (kg)
Area of room A (A
room A
) (m
2
)
Start
Use table 1 in chapter "Technical data" to
calculate the maximum refrigerant charge
(m
max
) (kg) allowed for room A.
Contact your dealer.
Use table 3 in chapter "Technical data" and
dm to calculate the minimum bottom opening
area for natural ventilation between room A
and room B (A
nv-min
) (cm
2
).
The unit can be installed in room A, and
without further room size or ventilation
requirements.
Determine the refrigerant amount that exceeds
m
max
(dm) (kg). (dm=m
c
–m
max
)
m
max
≥m
c
?
Yes
No
No
Use table 2 in chapter "Technical data" to
calculate the total minimum floor area
(A
min total
) (m
2
) required for the total refrigerant
charge (m
c
).
A
min total
≤A
room A
+A
room B
?
Yes
Input from installer:
Area of adjacent room B (A
room B
) (m
2
)
Unit can be installed in room A if you provide 2 openings (one at the bottom, one at the top) between room A and B to ensure natural ventilation. The openings
must comply with the following conditions:
Bottom opening (A
nv
):
Must be a permanent opening that cannot be closed.
Must be completely located between 0 and 300 mm from the floor.
Must be ≥A
nv-min
(minimum bottom opening area).
≥50% of the required opening area A
nv-min
must be ≤200 mm from the floor.
The bottom of the opening must be ≤100 mm from the floor.
If the opening starts from the floor, the height of the opening must be ≥20 mm.
Top opening:
Must be a permanent opening that cannot be closed.
Must be ≥50% of A
nv-min
(minimum bottom opening area).
Must be ≥1.5 m from the floor.
A B
A
nv
(≥A
nv-min
)
Min. 50%
of A
nv-min

Table of Contents