IO-DAPPS www.daikinac.com 14
Seng the Commissioning Setpoints
The commissioning setpoints set the operaonal setpoints and limits
for the BACnet™ Thermostat. Seng commissioning setpoints requires
entering Password 2.
NOTE: Not all setpoints in the following procedure are applicable
to all models of BACnet Thermostat. Those setpoints are
marked as (oponal).
Table 7: Seng the Commissioning Setpoints
Procedure Steps Display
Starng display
1. Start at the temperature display.
2. Enter Password 2. The display changes to the MAIN menu
display.
Choose and set the setpoints
1. From the MAIN menu, press either the or buon to
select SETPOINT.
2. Press Enter. The SETPOINT menu opens.
3. Choose and set each of the following setpoints.
OCC COOL – The cooling setpoint that is used as the
acve setpoint when the system is occupied
OCC HEAT – The heang setpoint that is used as the
acve setpoint when the system is occupied
UNOCC COOL – The cooling setpoint that is used as the
acve setpoint when the system is unoccupied
UNOCC HEAT – The heang setpoint that is used as the
acve setpoint when the system is unoccupied
MIN COOLING – The minimum cooling setpoint that a
user can select as the acve setpoint
MAX HEATING – The maximum heang setpoint that a
user can select as the acve setpoint
DIFFERENTIAL – The minimum value between the
cooling or heang setpoints. The BACnet Thermostat
will always maintain this dierence between setpoints
Program Set-Up