IO-DAPPS www.daikinac.com 14
Seng the Commissioning Setpoints
The commissioning setpoints set the operaonal setpoints and limits
for the BACnet™ Thermostat. Seng commissioning setpoints requires
entering Password 2.
NOTE: Not all setpoints in the following procedure are applicable
to all models of BACnet Thermostat. Those setpoints are
marked as (oponal).
Table 7: Seng the Commissioning Setpoints
Procedure Steps Display
Starng display
1. Start at the temperature display.
2. Enter Password 2. The display changes to the MAIN menu
display.
Choose and set the setpoints
1. From the MAIN menu, press either the ▲ or ▼ buon to
select SETPOINT.
2. Press Enter. The SETPOINT menu opens.
3. Choose and set each of the following setpoints.
• OCC COOL – The cooling setpoint that is used as the
acve setpoint when the system is occupied
• OCC HEAT – The heang setpoint that is used as the
acve setpoint when the system is occupied
• UNOCC COOL – The cooling setpoint that is used as the
acve setpoint when the system is unoccupied
• UNOCC HEAT – The heang setpoint that is used as the
acve setpoint when the system is unoccupied
• MIN COOLING – The minimum cooling setpoint that a
user can select as the acve setpoint
• MAX HEATING – The maximum heang setpoint that a
user can select as the acve setpoint
• DIFFERENTIAL – The minimum value between the
cooling or heang setpoints. The BACnet Thermostat
will always maintain this dierence between setpoints
Program Set-Up