IO-DAPPS www.daikinac.com 23
Procedure Steps Display
Calibrate the inputs
Choose CALIBRATION from the ADVANCED menu to calibrate an
input. The BACnet™ Thermostat includes two calibraon entries;
one for the internal temperature sensor and one for the oponal
remote temperature sensor connected to the RS terminal.
Enter a calibraon factor to adjust either input for
sensor inaccuracies.
• For a low input reading enter a posive correcon value
• For a high input reading enter a negave correcon value
Set the display blanking
Choose DISPLAY from the ADVANCED menu to set the display
appearance aer the last buon is pushed.
• BLANKING – Choose one of the blanking opons
— CLOCK – An analog clock replaces the temperature and
mode icons
— BACKLIGHT OFF – The display brightness changes to the level
set by DIM LEVEL aer the last buon interacon
— NONE – The temperature and mode icons always
remain visible
• DIM LEVEL – Sets the level of brightness of the display back light
if BACKLIGHT OFF is the selected blanking opon
Lockout user buons
Choose KEY LOCKOUT from the ADVANCED menu to limit the
accessibility to users with only Password 1, the user password.
• MODE/SETPOINT – Users with Password 1 cannot change any
value or mode
• MODE – Users with Password 1 cannot change the heang/
cooling, fan, or occupancy modes
• NONE – Users with Password 1 have full access to acve
setpoints, heang/cooling, fan, and occupancy modes
Program Set-Up