IO-DAPPS www.daikinac.com 23
Procedure Steps Display
Calibrate the inputs
Choose CALIBRATION from the ADVANCED menu to calibrate an
input. The BACnet™ Thermostat includes two calibraon entries;
one for the internal temperature sensor and one for the oponal
remote temperature sensor connected to the RS terminal.
Enter a calibraon factor to adjust either input for
sensor inaccuracies.
For a low input reading enter a posive correcon value
For a high input reading enter a negave correcon value
Set the display blanking
Choose DISPLAY from the ADVANCED menu to set the display
appearance aer the last buon is pushed.
BLANKING – Choose one of the blanking opons
CLOCK – An analog clock replaces the temperature and
mode icons
BACKLIGHT OFF – The display brightness changes to the level
set by DIM LEVEL aer the last buon interacon
NONE – The temperature and mode icons always
remain visible
DIM LEVEL – Sets the level of brightness of the display back light
if BACKLIGHT OFF is the selected blanking opon
Lockout user buons
Choose KEY LOCKOUT from the ADVANCED menu to limit the
accessibility to users with only Password 1, the user password.
MODE/SETPOINT – Users with Password 1 cannot change any
value or mode
MODE – Users with Password 1 cannot change the heang/
cooling, fan, or occupancy modes
NONE – Users with Password 1 have full access to acve
setpoints, heang/cooling, fan, and occupancy modes
Program Set-Up