Operation manual BRC2E52C7 / BRC3E52C7
37
4P368042-1 - 2014.02
Menu Manipulation
Setpoint Range Setting
1
1/2
Energy Saving List
Setpoint Range
Setback Condition
Sensing Sensor(Low)
Sensing Sensor(Stop)
Setpoint Auto Reset
Energy Saving Options
SettingReturn
Display the Energy Saving Options (See "Energy
Saving List" on page 36).
Press the
(Up/Down) buttons to select
Setpoint Range and press the Menu/Enter
button.
2
16°C – 32°C
16°C – 32°C
Setpoint Range
SettingReturn
Cool
Heat
Press the (Up/Down) buttons to change the
cooling or heating temperature setpoint range.
Move the cursor using the
(Left/Right)
buttons.
Press the Menu/Enter button when all changes are
made. The conrmation screen will appear.
Note
The default setpoint range restriction is [16°C→32°C]. This setpoint range is the general
setpoint range and is as a result always active regardless of whether Setpoint Range is
enabled or disabled.
The default setpoint range for setback operation is [33°C→37°C] for cooling and [10°C→15°C]
for heating. This setpoint range cannot be changed.
3
NoYes
Setpoint Range
Save the settings?
SettingReturn
Press the (Left/Right) buttons to select Yes .
Press the Menu/Enter button to conrm the
settings and to return to the Basic Screen.
Operation Method
This function should not be used when a centralised controller is connected.