EasyManua.ls Logo

Daikin BRC2E52C - Page 39

Daikin BRC2E52C
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BRC2E52C7 / BRC3E52C7 Operation manual
4P368042-1 - 2014.02
38
Menu Manipulation
Setback Condition
1
1/2
Energy Saving List
Setpoint Range
Setback Condition
Sensing Sensor(Low)
Sensing Sensor(Stop)
Setpoint Auto Reset
Energy Saving Options
SettingReturn
Display the Energy Saving Options (See "Energy
Saving List" on page 36).
Press the
(Up/Down) buttons to select
Setback Condition and press the Menu/Enter
button.
2
-2°C
Recovery Differential
Cool Heat
+2°C
Setback Condition
SettingReturn
Press the (Up/Down) buttons to change the
differential for setback operation.
Move the cursor using the
(Left/Right)
buttons.
Press the Menu/Enter button when all changes are
made. The conrmation screen will appear.
3
NoYes
Setback Condition
Save the settings?
SettingReturn
Press the (Left/Right) buttons to select Yes .
Press the Menu/Enter button to conrm the
settings and to return to the Basic Screen.
Note
The default setpoint range restriction is [16°C→32°C]. This setpoint range is the general
setpoint range and is as a result always active regardless of whether Setpoint Range is
enabled or disabled.
The default setpoint range for setback operation is [33°C→37°C] for cooling and [10°C→15°C]
for heating. This setpoint range cannot be changed.
Operation Method
This function should not be used when a centralised controller is connected.

Related product manuals