Operation manual BRC2E52C7 / BRC3E52C7
39
4P368042-1 - 2014.02
Menu Manipulation
Sensing Sensor(Low)
This function cannot be used when group control is active.
In case of a simultaneous operation system, the system is controlled by the
sensing sensor mounted in the master indoor unit.
Operation Method
1
1/2
Energy Saving List
Setpoint Range
Setback Condition
Sensing Sensor(Low)
Sensing Sensor(Stop)
Setpoint Auto Reset
Energy Saving Options
SettingReturn
Display the Energy Saving Options (See "Energy
Saving List" on page 36).
Press the
(Up/Down) buttons to select
Sensing Sensor(Low) and press the Menu/Enter
button.
2
Adjust Cool SP:
Adjust Time Cool:
Limit Cool SP:
Adjust Heat SP:
Adjust Time Heat:
Limit Heat SP:
Sensing Sensor(Low)
1.0°C
15 min
35°C
1.0°C
15 min
15°C
SettingReturn
Press the (Up/Down) buttons to set the
energy saving operation when the sensor detects
an absence.
Move the cursor using the
(Left/Right)
buttons.
Press the Menu/Enter button when all changes are
made. The conrmation screen will appear.
Example (settings on the left apply):
If the sensor determines that there is no person in
the room during cooling operation, the cooling
setpoint temperature will automatically increase by
1°C every 15 minutes until the cooling setpoint
temperature is 35°C. On the Basic Screen, the
cooling setpoint temperature will not change.
3
NoYes
Sensing Sensor(Low)
Save the settings?
SettingReturn
Press the (Left/Right) buttons to select Yes .
Press the Menu/Enter button to conrm the
settings and to return to the Basic Screen.