40 Installation Manual 3P581074-2D
DGE601A52
English
3.4.2 Wiring specications
• Cable type: Ordinary tough rubber sheathed cord (60245 IEC 53) equivalent or
higher
Ordinary polyvinyl tough chloride sheathed cord (60227 IEC 53) equiva-
lent or higher
• Core thickness: Power wire: 1.0 - 2.0mm²
Earth lead: Size must comply with local codes and be the same
thickness as the power wire.
• Earth lead terminal treatment: Be sure to use a round crimp-type terminal (2-M4).
• Power supply voltage: Single phase 100 to 240VAC (at 50/60Hz)
• Electric power consumption: Less than 3W (per 1 unit)
• Earth leakage breaker: Rated current 10A (Rated sensitivity current 30mA operat-
ing time 0.1 sec or less)
3mm minimum contact gap and all-pole disconnection
CAUTION
• Be sure to install an earth leakage breaker capable of shutting down the
power supply to the entire system, as required.
• Turning on/off the earth leakage breaker turns on/off the power supply to
the DGE601A52.
• Select an earth leakage breaker that offers protection against overcurrent
and short-circuit. When the earth leakage breaker only serves as earth
device, make sure to also install a wiring interrupter.
• The power supply requires earth leakage breaker installation and earth wire
connection. After installing an earth leakage breaker, be sure to connect
only the DGE601A52 to it.
• To prevent accidents due to wire breakage or disconnection, secure the
power supply cables with clamps.
• Be sure to connect the earth wire.
• Do not connect the earth wire to gas or water pipes, lighting rods, or tele-
phone earth wires.
• Replace the unit when the unit cannot be turned on due to the blowing of
the electrical fuse.
NOTE
A power supply cable is not provided with the unit.
Use a 3-core power supply cable with a core thickness of 1.0 - 2.0mm² that complies
with local standards and is rated at 300VAC or higher.