EasyManua.ls Logo

Daikin Enfinity VFC - ADDITIONAL ACCESSORIES - GENERAL

Daikin Enfinity VFC
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.DaikinApplied.com 31 EnnityVerticalWaterSourceHeatPumps IM 930-6
Motorized Isolation Valve & Relay
Themotorizedvalvekitisavailableasafactory-installed
andwiredoptionormaybeorderedasaeld-installed
accessory.
WiredasshowninFigure29,themotorizedvalvewillopen
onacallforcompressoroperation.Valvesforunitsizes
009to019are1/2"whileunitsizes024to070are3/4".
UsingaNormallyClosed(N/C),poweropenvalve,wire
asillustratedinFigure29.
Figure 29: Normally Closed, Power Open Motorized Valve
& Relay Wiring
Actuator&
ValveAssembly
Anti-shortBushing
Connector
Conduit
Pin(s),female
plugintoreceptacle
congurationbelow
Connector
Anti-short
Bushing
Note: Connectors on valve must be cut off and stripped
back and the wires twisted to make connections
to the IV/PR Terminals
Pump Restart Relay Kit P/N 061419001
TheMicroTechIIIunitcontrollerhasaninternalPump
RestartRelayconnectedtoH8,Pin2fortheNormally
Open(N/O)terminaloftheinternalrelay.
ConnecttoH8,Pin1fortheNormallyClosed(N/C)
terminaloftheinternalrelay.
Theoutputoftheinternalpumprestartrelayis24-
voltsACandtheoutputisnotavailablewhentheH8
connectionisusedtocontrolamotorizedvalve.
Multiple Unit Control (up to 3 units)
(P/N 056794201)
Themultipleunitcontrolboardisanaccessoryusedwhen
upto3-unitsarecontrolledfromasinglethermostat.
Typicallythecontrolpanelandboardiscentrallymounted
betweentheunitsandthermostat.Amaximumof2
boardsmaybeusedtogetherifupto6-unitsmustbe
connectedandcontrolledfromasinglethermostat.For
detailedinstallationinstructionsrefertoIM952.
ThisversionofthecontrolusesVACrelaysandshould
notbeusedincombinationwithanyotheraccessoriesor
equipmentthatrequireVDCconnections.
Figure 30: Multiple Unit Control Panel and Board
Themultipleunitcontrolboardprovidesthecomponents
necessarytoprotecttheMicroTechIIIunitcontrollerfrom
electricaldamagethatmayoccurwhenusingstandard
off-the-shelfrelays.
Donotusetheunoccupied(U-terminal)featurewiththe
multiple unit control board.
Figure 31: Wiring Multiple Unit Control Board (MUCP)
M
ultiple Unit Control Panel
Circuit Board
MicroTech III Unit Control Board
Low Voltage Terminal Strip
C
G
Y1
Y2W1
W2
A
R
O
Thermostat Terminals
W1
Y1
W2
Y2
G
-
C
+
R
RYGW
RYGW
RYGW
RYGWC
K3
K2
K1
TB3
TB4
TB2
TB1
C
G
Y1
Y2W1
W2
A
R
O
C
G
Y1
Y2W1
W2
A
R
O
TB2 - Unit #1
TB2 - Unit #2
TB2 - Unit #3
Notes: Dotted lines represent low voltage (Class II)
wiring; a color-coded thermostat cable is recom-
mended.
MUCP may be mounted horizontally or vertically
on heat pump cabinet or any convenient surface.
Do not use if using night setback.
Thermostat must be A.C. voltage.
additional aCCessories – general

Table of Contents

Related product manuals