EasyManua.ls Logo

Daikin Enfinity VFC - Start-Up

Daikin Enfinity VFC
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
start-uP
www.DaikinApplied.com 23 EnnityVerticalWaterSourceHeatPumps IM 930-6
Unitsmustbecheckedforwaterleaksuponinitialwatersystem
start-up.Waterleaksmaybearesultofmishandlingordamage
duringshipping.Failurebytheinstallingcontractortocheckfor
leaksuponstart-upofthewatersystemcouldresultinproperty
damage.
CAUTION
1. Openallvalvestofullopenpositionandturnon
powertotheunit.
2. Setthethermostatfor"FanOnly"operationby
selecting"Off"atthesystemswitchand"On"atthe
fanswitch.If"Auto"fanoperationisselected,the
fanwillcyclewiththecompressor.
3. Forthoseunitsthathavetwo-speedmotors,
reconnectforlowspeedoperationifnecessary
4. Setthermostatto“Cool.”Ifthethermostatisan
automaticchangeovertype,simplysetthecooling
temperaturetothelowesttemperature.Onmanual
changeovertypes,additionallyselect“Cool”atthe
systemswitch.
Again,manyunitshavetimedelayshelpprotectthe
compressor(s)againstshortcycling.
Afterafewminutesofoperation,checkthe
dischargegrillesforcoolairdelivery.Measure
thetemperaturedifferencebetweenenteringand
leavingwater.Itshouldbeapproximately1-1⁄2
timesgreaterthantheheatingmodetemperature
difference.Forexample,ifthecoolingtemperature
differenceis15°F(8°C),theheatingtemperature
differenceshouldbe10°F(5°C).
Withoutautomaticowcontrolvalves,targeta
coolingtemperaturedifferenceof10°Fto14°F(5°C
to8°C).Adjustthecombinationshutoff/balancing
valveinthereturnlinetoawaterowratewhichwill
resultinthe10˚Fto14°F(5°Cto8°C)difference.
5. Setthermostatto“Heat.”Ifthethermostatisthe
automaticchangeovertype,setsystemswitchto
the“Auto”positionanddepresstheheatsettingto
thehighesttemperature.Someunitshavebuilt-in
timedelayswhichpreventthecompressorfrom
immediatelystarting.Withmostcontrolschemes,
thefanwillstartimmediately.Afterafewminutesof
compressoroperation,checkforwarmairdelivery
atdischargegrille.Ifthisisa“coldbuilding”start-
up,leaveunitrunninguntilreturnairtotheunitisat
least65°F(18°C).

Table of Contents

Related product manuals