IM 930-6 EnnityVerticalWaterSourceHeatPumps 22 www.DaikinApplied.com
Figure 21: Sizes 042-070 (575/60/1)
Unit Size 042 through 070 (265/60/1),
(208/230/1) & (208/230/3)
Fanmotorsonunitsizes042-070involtages265/60/1,
208/230/1and208/230/3(Figure22)allhaveave-
positionterminalblock.Inordertochangebetweenhigh
andlowspeed,interchangethewiresontheblackand
redterminals.
Figure 22: Sizes 042-070 (265/60/1), (208/230/1) (208/230/3)
Unit Size 024 through 036 (208/230/3)
Fanmotorsonunitsizes024-036involtages208/230/3
(Figure23)allhaveafour-positionterminalblock.
Inordertochangebetweenhighandlowspeed,
interchangethewiresontheblackandredterminals.
Figure 23: Sizes 024-036 (208/230/3)
Notes: All motors have a wiring label that is keyed for
proper wiring operation. Check unit wiring dia-
gram (on electrical access panel) for proper unit
operation. Not all labels are the same.
Units leaving the factory are wired for high or low
fan speed (see Table 13 on page 21 for fan
speed settings).
Label is located on the back of the terminal block.
(Optional) ECM Motor
TheECMmotorwillmaintaintheratedairowasstatic
pressureincreasesordecreaseswithintheunit’s
operatingrange.Contactthefactoryat315-253-2771or
800-432-1342ifanalternateairowsettingisrequired.
Prior to start-uP