ESIE98–06A Troubleshooting
Part 3 Troubleshooting 3–21
33
4
5
1
An overview of the fault indications and safeties is given in ‘Overview of Fault Indications and Safeties’
on page 3-7.
High pressure
switch
water flow too low in heating
water temperature too high in
heating
defective condenser fan
operation in cooling
dirty or blocked condenser
operation out of range
pump operation
water flow (blocked valves)
flow switch operation
operation condition
outdoor air temperature < 43 °C
leaving condenser water < 25 °C
state of the condenser (clean)
Flow switch or
pump contact
damaged flow switch
incorrect pump operation
incorrect field wiring
defective control devices
(pump relay)
flow switch
pump operation
field wiring
control devices
Discharge ther-
mal protector
Refrigerant shortage
Operation out of range
Refrigerant leak
Operation condition
Fan thermal
protector
Blocked fan
Blocked condenser
State of the fans (free rotation)
State of the condenser
Reverse phase
protection
Incorrect phase direction
One phase missing
Swap two phases
Connect the loose phase
Problem Possible causes Items to be checked