Daikin EUWA/Y5-30HB/C(Z) - Procedure for PCB Changing (EUWA;Y15-30 HC(Z))

Daikin EUWA/Y5-30HB/C(Z)
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting ESIE98–06A
3–28 Part 3 Troubleshooting
3
1
3
4
5
4.6 Procedure for PCB Changing (EUWA/Y15-30HC(Z))
Changing the PCB To change the PCB, proceed as follows:
Entering the factory
menu
The factory menu is used to set up the identification parameters of the unit according to its PCB. To
enter the factory menu, proceed as follows:
For more information concerning the controller, refer to ‘The EUWA/Y15-30HC(Z) Controller’ on
page 2-26.
Load defaults When you have entered the factory menu, proceed as follows:
Initialization Follow the next screens to insert the settings of the former PCB.
Step Action
1 Remove the connections of the old PCB.
2 Remove the old PCB.
3 Place the new PCB in the same way as the old PCB.
4 Reconnect the PCB.
Step Action Result
1 Put on the power supply. After a few seconds, the user terminal
will enter the read-out menu. Refer to
a Read-out Menu’ on page 2-31.
2 Press a and e simultaneously for 5
seconds.
The leds above a and e light up.
(also when you release the buttons)
3 Scroll using h to go to 1914.
4 Press j. You have entered the factory menu.
Step Action Action
1 Scroll downwards using h to go to the next
screen.
2 Press j 3 times. The cursor is blinking on N on the
load defaults line.
3 Scroll downwards using h to change N into Y.
4 Press j. When Y becomes N again, all the
default values are loaded into the
new PCB.
5 Scroll upwards using h to go to the first screen. You can start initialization.
6 Press j.