General Outline ESIE98–06A
1–10 Part 1 – System Outline
3
11
4
5
1.3 Electrical specifications
EUWA5-30HB/C In the following table you will find the electrical specifications of chiller types EUWA5-30HB/C:
Nominal conditions The nominal conditions are as follows:
■ entering/leaving water temperature 12/7 °C
■ ambient air temperature 35 °C
■ power input is total input:
compressor + control circuit
■ leaving evaporator water temperature from 4 °C to 20 °C (pull-down condition to 25 °C).
Operation range The operation range contains a leaving evaporator water temperature from 4 °C till 20 °C (pull-down
condition till 25 °C).
Model
EUWA5HBW1
/EUWA5HBT1
EUWA8HBW1
/EUWA8HBT1
EUWA10HBW1
/EUWA10HBT1
EUWA15HCW1
/EUWA15HCT1
EUWA20HCW1
/EUWA20HCT1
EUWA25HCW1
/EUWA25HCT1
EUWA30HCW1
/EUWA30HCT1
Compressor
phase 3~
Voltage 220 - 380 V
starting current 49 A/88 A 79 A/142 A 109 A/183 A 49 A/88 A-
109 A/183 A
109 A/183 A 49 A/88 A-
109 A/183 A
109 A/183 A
max. running cur-
rent
10 A/17 A 18 A/28 A 21 A/34 A 10 A/17 A+
21 A/34 A
2x21 A/34 A 2x21 A/34 A10
A/17 A+
3x21 A/34 A
starting method direct on line
voltage 400 V/230 V
nominal running
current
5.5 A/9.5 A 9.7 A/16.8 A 12.5 A/21.7 A 5.5 A/9.5 A+
12.5 A/21.7 A
2x
12.5 A/21.7 A
2x
12.5 A/21.7 A+
5.5 A/9.5 A
3x
12.5 A/21.7 A
Nominal distribution system voltage
phase 3N~/3~
frequency 50 Hz
voltage 400 V/230 V
voltage tolerance ±10 V
Control circuit
phase 1~
recommended
fuses
factory installed
voltage 230 V
Unit
nominal running
current
8 A/12 A 13.2 A/20.3 A 16 A/25.2 A 23 A/36.2 A 31 A/49.4 A 38 A/60.4 A 46 A/73.6 A
recommended
fuses
3 x 20 aM/
3 x 25 aM/
3 x 25 aM/
3 x 40 aM
3 x 32 aM/
3 x 50 aM
3x40aM/
3 x 63 aM
3 x 50 aM/
3 x 80 aM
3 x 63 aM/
3 x 100 aM
3 x 80 aM/
3 x 125 aM
max. running cur-
rent
12.5 A/19.5 A 21.5 A/31.5 A 24.5 A/37.5 A 36 A/56 A 48 A/74 A 59.5 A/92.5 A 71.5 A/110.5 A