ESIE98–06A General Outline
Part 1 System Outline 1–7
3
1
4
5
1
(1)
: Minimum water volume standard thermostat difference setting of 3 K. For reduced setting multiply
this water volume by (3/new setting). Minimum allowable setting = 0.1 K.
(2)
: The sound pressure level is measured using a microphone at a certain distance from the unit. It is
a relative value, depending on the distance and acoustic environment.
(3)
: The sound power level is an absolute value indicating the “power”, which a sound source
generates.
Nominal conditions The nominal conditions are as follows:
entering/leaving chilled water temperature 12/7 °C, ambient air temperature 35 °C
entering/leaving condenser water temperature 45/50 °C; ambient 7 °CDB/6 °CWB
power input is total input: compressor + control circuit
sound pressure level is measured at a height of 1.5 m and a distance of 1 m in front of the unit.
Operation range The operation range contains:
a leaving evaporator water temperature from 4 °C till 20 °C (pull-down condition till 25 °C)
a leaving condenser water temperature from 35 °C till 55 °C.
refrigerant charge 3.6 kg 5.1 kg 5.9 kg 5.9+3.6 kg 2x5.9 kg 2x5.9+3.6 kg 3x5.9 kg
refrigerant control capillary tube
oil type SUNISO 4GSDID-K
oil charge volume 1.5 l 2.7 l 2.7 l 2.7+1.5 l 2x2.7 l 2x2.7+1.5 l 3x2.7 l
n° of circuits 1112233
Dimensions
(h x w x d)
1444 x 645 x
700 mm
1220 x 1290x
700 mm
1444 x1290 x
700 mm
1535 x 1930 x
700 mm
1535 x 2575 x
700 mm
1535 x 3220 x
700 mm
1535 x 3865 x
700 mm
Weight
machine weight 140 kg 208 kg 240 kg 390 kg 530 kg 675 kg 800 kg
operation weight 142 kg 210 kg 143 kg 395 kg 536 kg 683 kg 809 kg
Casing
material polyester coated / galvanised steel plate / ± RAL 7044
colour ivory white / Munsell code 5Y7.5/1
Sound pressure
level
(2)
50 dB 59 dB 59 dB 59 dB 62 dB 62 dB 64 dB
Sound power
level
(3)
69 dB 78 dB 78 dB 78 dB 81 dB 81 dB 83 dB
Safety devices
high pressure switch
discharge temperature control
freeze-up protection thermostat
compressor motor overcurrent relay
fan thermal protector
anti-recycling and guard timer
digital display controller with electronic temperature control
reverse phase protector
internal fuses for each circuit.
Model EUWY5HB EUWY8HB EUWY10HB EUWY15HC EUWY20HC EUWY25HC EUWY30HC