General Outline ESIE98–06A
1–12 Part 1 System Outline
3
11
4
5
EUWA5-30HB/CZ In the following table you will find the electrical specifications of chiller types EUWA5-30HB/CZ:
Nominal conditions The nominal conditions are as follows:
entering/leaving water temperature 12/7 °C
ambient air temperature 35 °C
power input is total input:
compressor + control circuit.
Operation range The operation range contains a leaving evaporator water temperature from 4 °C till 20 °C (pull-down
condition till 25 °C).
Model EUWA5HBZ EUWA8HBZ EUWA10HBZ EUWA15HCZ EUWA20HCZ EUWA25HCZ EUWA30HCZ
Compressor
phase 3~
Voltage 220 - 380 V
starting current 49 A/88 A 79 A/142 A 109 A/183 A 49 A/88 A-
109 A/183 A
109 A/183 A 49 A/88 A-
109 A/183 A
109 A/183 A
max. running current 10 A/17 A 18 A/28 A 21 A/34 A 10 A/17 A+
21 A/34 A
2x21 A/34 A 2x21 A/34 A+
10 A/17 A+
3x21 A/34 A
starting method direct on line
voltage 400 V/230 V
nominal running current 6.6 A/11.4 A 10.4 A/18 A 13.1 A/22.8 A 6.6 A/11.4 A+
13.1 A/22.8 A
2x
13.1 A/22.8 A
2x
13.1 A/22.8 A+
6.6 A/11.4 A
3x
13.1 A/22.8 A
Nominal distribution system voltage
phase 3N~/3~
frequency 50 Hz
voltage 400 V/230 V
voltage tolerance ±10 V
Control circuit
phase 1~
recommended fuses factory installed
voltage 230 V
Unit
nominal running current 7 A/12.3 A 11.2 A/19.7 A 13.9 A/24.4 A 20.9 A/36.7 A 27.8 A/48.8 A 34.8 A/61.1 A 41.7 A/73.2 A
recommended fuses 3 x 20 aM/
3 x 25 aM/
3 x 25 aM/
3 x 40 aM
3x32aM/
3 x 50 aM
3 x 40 aM/
3 x 63 aM
3 x 50 aM/
3 x 80 aM
3 x 63 aM/
3 x 100 aM
3 x 80 aM/
3 x 125 aM
max. running current 11.3 A/18.3 A 20.5 A/30.5 A 23.5 A/36.5 A 34.7 A/54.7 A 46.9 A/72.9 A 58.1 A/91.5 A 70.3 A/109.3 A
starting current 52 A/91 A 84 A/147 A 114 A/188 A 126 A/207 A 138 A/225 A 150 A/244 A 162 A/162 A