Field Setting from Remote Controller ESIE15-13B
64 Field Setting
2.1.3 Remote controller settings
Level Setting Code Function Adjustment Description Info
Remote controller BRC1E
Remote controller setting (BRC1E)
1b 8 Automatic summer/
wintertime changeover
01 No automatic changeover
02 Automatic changeover
active
03 Setting menu available in
Extended functions
1x RETURN -> Extended
functions -> Summertime
a"Away from Home
function" can be freely
selected in main menu
using RETURN.
You can select start point
for heating between 5°C
and 10°C and for cooling
between 35°C and 40°C.
01 "Away from Home menu" is
not available
02 "Away from Home menu" is
available in main menu
You must also activate the
"Away from Home
function" in the 1e-2 setting
1x RETURN -> Away from
Home function
b Clock display in the remote
controller
01 Clock is displayed in
remote controller with
detail display ON
02 Clock is not displayed Available as from software
04.003
1c 0 Available selection in the
detail display
01 Room temperature not
available
02 Room temperature
available
You can determine which
sensors are displayed
using setting 1c-1
1x RETURN -> Extended
functions -> Detail display
1 Use remote controller
temperature sensor in
"Detail display", "Away
from Home function" and
"Limit operation"
01 Suction air thermistor
(R1T)
If the detail display is
activated, the suction air
thermistor should be used.
02 Remote controller sensor
3 Remote controller keylock 01 Level 2
Free keys:
Mode
Setpoint
On/Off
To activate or deactivate
the keylock starting 1x right
arrow and then right arrow
again, press Back, Mode,
Fan simultaneously.
If the keylock is active, the
key symbol appears when
locked keys are pressed.
02 Level 3
Free keys:
On/Off
4 Backlighting 01 Off
02 On as soon as a key is
pressed
Backlight goes out after 20
seconds.
03 Permanently On
6 Display 01 Display is always available
02 Display switches off after 5
minutes and is reactivated
by pressing a key