ESIE15-13B Field Setting from Remote Controller
Field Setting 65
Level Setting Code Function Setting Description Info
Remote controller BRC1E
Remote controller setting (BRC1E)
1e 1 Unit of temperature 01 °C
02 Optional choice of °C or °F
in "Extended functions"
menu option
1x RETURN -> Extended
functions -> Unit of
temperature
2"Away from Home
function"
After being activated
below/above the
temperature set in the main
menu (see setting 1b-a),
the "Away from Home
function" switches on the
interior unit and the system
runs without setpoint until
the temperature is once
again within the safe
range. (Heating 5°C - 10°C
/cooling 35°C - 40°C)
Only for master units in the
system (if necessary,
consider setting 22-9)
01 Not available To activate the Away from
Home function, press right
arrow for 5 seconds.
In the display you will see
To deactivate, press right
arrow again for 5 seconds.
02 Available for heating mode
03 Available for cooling mode
04 Available for heating and
cooling mode
4 Weekly timer 01 Weekly timer is not
available
If the sequence timer is
also deactivated under 1e-
6, the "Timer settings"
menu option disappears
02 Weekly timer is available 1x RETURN -> Timer
adjustment -> Weekly timer
5 Clock display options 01 24-hour display
02 You can choose between
24-hour or 12-hour display
in the "Extended functions"
menu option
1x RETURN -> Extended
functions -> Time display
6 Sequence timer 01 Sequence timer is not
available
If the weekly timer is also
deactivated under 1e-4,
the "Timer settings" menu
option disappears
02 Sequence timer is
available
1x RETURN -> Timer
adjustment -> Sequence
timer
a Sensor calibration of
remote controller sensor in
the master remote
controller
01 -3 K As from BRC1E software
ver.04.00.03
02 -2.5 K
03 -2 K
04 -1.5 K
05 -1 K
06 -0.5 K
07 ±0 K
08 +0.5 K
09 +1 K
b Sensor calibration of
remote controller sensor in
the slave remote controller
01 -3 K As from BRC1E software
ver.04.00.03
02 -2.5 K
03 -2 K
04 -1.5 K
05 -1 K
06 -0.5 K
07 ±0 K
08 +0.5 K
09 +1 K

Table of Contents

Other manuals for Daikin FAQ71CVEB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ71CVEB and is the answer not in the manual?

Daikin FAQ71CVEB Specifications

General IconGeneral
BrandDaikin
ModelFAQ71CVEB
CategoryAir Conditioner
LanguageEnglish

Related product manuals