5.1.11 Hall IC Check
Check No.16 1. Check the connector connection.
2. With the power ON, operation OFF, and the connector connected, check the following.
Output voltage of about 5 V between pins 1 and 3.
Generation of 3 pulses between pins 2 and 3 when the fan motor is operating.
Failure of (1) Æ faulty PCB Æ Replace the PCB.
Failure of (2) Æ faulty Hall IC Æ Replace the fan motor.
Both (1) and (2) result Æ Replace the PCB.
Gray (power supply)
Purple (signals)
Blue (grounding)