291
■
An indoor unit cannot be started using remote controller.
• Remote controller may be disabled.
An indoor unit may not be started/stopped, or its operation mode, set temperature changed
depending on the remote controller operation settings.
Check remote controller operation settings from the Standard View screen (List View) or R/C
Prohibition tab of the Detailed Setup screen.
For details of remote controller operation settings, see page 41.
■
An area or indoor unit cannot be operated from the Standard View screen.
• Check the Standard View screen for the “Emergency Stop” icon, as shown in the gure below.
“Emergency Stop” is displayed in the following cases:
An emergency stop order has been received by the central control device (centralized
management controller, ON/OFF controller, etc), including the iTM. If an emergency stop order
is received, all air conditioners connected to the iTM will stop by default. Furthermore,
operating air conditioners from a central control device or remote controller is impossible while
an emergency stop order is present.
The “Emergency Stop” icon will disappear and operation from the iTM will become possible
when the emergency stop order stops.