User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
292
Starting/stopping air conditioners is not possible from the Standard View screen.
Check the monitoring screen for the “Central controlled” sign, as shown in the gure below.
In “Central controlled”, iTM is left for monitoring only if a higher level central device (Interface
for use in BAC net, etc.) is given priority.
The Setting button is not available for touch on the Standard View screen.
“Prohibit Manual Operation” may be set up for the selected management point.
If “Manual Disable” is displayed in the List View as shown in the gure below, “Prohibit Manual
Operation” is set up.