EasyManua.ls Logo

Daikin MicroTech III DPS - Appendix: Fan Failure Codes (Continued); Phase Failure and Voltage Issues

Daikin MicroTech III DPS
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OM 1263 • MICROTECH UNIT CONTROLLER 102 www.DaikinApplied.com

PHA = Phase failure
UzLow = DC-Link Undervoltage
UzHigh = DC-Link Overvoltage
UeHigh = Mains Overvoltage
UeLow = Mains Undervoltage
Question: • Can the main voltage be measured at any spot; a data logger may be helpful.
No: Measure the voltage at the power supply input of the concerned fan.
Corrective: • Reset the failure; re-start the motor and observe it.
• If applicable, lter out the source of disturbing signal.
Repeated occurrence:
Question: • Do other fans show the same failure?
• How often does the failure occur?
• Get big electrical consumer loads switched at the same time when the failure occurs in the surrounding area?
Are compressors or large asynchronous motors applied within the arrangement?
Yes: Systematic search for external disturbance voltage peaks; If applicable, usage of data logger for a longer
period and analysis of the measured values.
Are the voltage values within the specied range?
No: It seems to be a hardware problem of the fan. Fan need to be replaced.

Table of Contents

Related product manuals