OM 1263 • MICROTECH UNIT CONTROLLER 88 www.DaikinApplied.com

ERROR CODE: L8 – Momentary Overcurrent of Inverter Compressor
Remote
Controller
Display
L8
Method of
Malfunction
Detection
Malfunction is detected from current owing in the power transistor.
Malfunction
Decision
Condition
When overload in the compressor is detected. (Inverter secondary current 16.1A)
For 460V units
(1) 19.0A and over continues for 5 seconds.
(2) 16.1A and over continues for 260 seconds.
For 230V units
(1) A current of 33.5A or more continues for a period of consecutive 5 sec.
(2) A current of 27.6A or more continues for a period of consecutive 260 sec.
Supposed
Causes
Compressor overload
Compressor coil disconnected
Defect of inverter PC board
Faulty compressor