Daikin MicroTech III DPS - Troubleshooting: Error Code P4; P4 - Inverter Radiating Fin Temperature Rise Sensor

Daikin MicroTech III DPS
114 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OM 1263 • MICROTECH UNIT CONTROLLER 94 www.DaikinApplied.com

ERROR CODE: P4 – Malfunction of Inverter Radiating Fin Temperature Rise Sensor
Remote
Controller
Display
P4
Method of
Malfunction
Detection
Resistance of radiation n thermistor is detected when the compressor is not operating.
“P4” will be displayed by pressing the inspection button.
Supposed
Causes
● Defect of radiator n temperature sensor
● Defect of inverter PC board
● Faulty inverter compressor
● Faulty fan motor