OM 1263 • MICROTECH UNIT CONTROLLER 94 www.DaikinApplied.com

ERROR CODE: P4 – Malfunction of Inverter Radiating Fin Temperature Rise Sensor
Remote
Controller
Display
P4
Method of
Malfunction
Detection
Resistance of radiation n thermistor is detected when the compressor is not operating.
P4” will be displayed by pressing the inspection button.
Supposed
Causes
Defect of radiator n temperature sensor
Defect of inverter PC board
Faulty inverter compressor
Faulty fan motor