OM 1263 • MICROTECH UNIT CONTROLLER 86 www.DaikinApplied.com

ERROR CODE: L5 – Momentary Overcurrent of Inverter Compressor
Remote
Controller
Display
L5
Method of
Malfunction
Detection
Malfunction is detected from current owing in the power transistor.
Malfunction
Decision
Condition
When an excessive current ows in the power transistor.
(Instantaneous overcurrent also causes activation.)
Supposed
Causes
Defect of compressor coil (disconnected, defective insulation)
Compressor start-up malfunction (mechanical lock)
Defect of inverter PC board