www.DaikinApplied.com 71 OM 1263 • MICROTECH UNIT CONTROLLER
ACS1 DataRcvd
Upon power up the IFB board receives initial conrmation
data from all the devices that are connected to the ACS1
channel. Problems with this conrmation are indicated with this
parameter. There are 8 possible conditions indicated. These
are described as follows:
ErrAll: IFB did not receive initial conrmation data from
any of the devices on the ACS1 communication channel.
This generally indicates a physical break in the ACS1
communication loop wiring between the IFB board and the
A4P and A5P boards or lack of power to both the A4P and A5P
boards.
F1F2Err: IFB did not receive initial conrmation data from
the OF2 nor OF1 on the ACS1 communication channel. This
generally indicates a defect in both the boards controlling OF1
(A4P or A5P) and OF2 (A5P).
INVF2Err: IFB did not receive initial conrmation data from
the INV nor OF2 on the ACS1 communication channel. This
generally indicates a defect in both the boards controlling INV
(A4P) and OF2 (A5P).
F2Err: IFB did not receive initial conrmation data from the
OF2 on the ACS1 communication channel. This generally
indicates a defect in the board controlling OF2 (A5P).
INVF1Err: IFB did not receive initial conrmation data from
the INV or OF1 on the ACS1 communication channel. This
generally indicates a defect in both the boards controlling INV
(A4P) and OF1 (A4P or A5P).
F1Err: IFB did not receive initial conrmation data from the
OF1 on the ACS1 communication channel. This generally
indicates a defect in the board controlling OF1 (A4P or A5P).
INVErr: IFB did not receive initial conrmation data from the
INV on the ACS1 communication channel. This generally
indicates a defect in the board controlling INV (A4P).
AllOK: All initial conrmation data has been received from all
the devices on the ACS1 communication loop.
ACS3 DataRcvd
Upon power up the IFB board receives conrmation data
from all the devices that are connected to the ACS3 channel.
Problems with this conrmation are indicated with this
parameter. There are 2 possible conditions indicated. These
are described as follows:
Error: IFB did not receive initial conrmation data from
the EVB board on the ACS3 communication channel.
This generally indicates a physical break in the ACS3
communication loop wiring between the IFB board and the
EVB board, lack of power to the EVB board or a defect in the
EVB board.
OK: All initial conrmation data has been received from all the
EVB board on the ACS3 communication channel.
Fig 1 note

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech III DPS and is the answer not in the manual?

Daikin MicroTech III DPS Specifications

General IconGeneral
BrandDaikin
ModelMicroTech III DPS
CategoryController
LanguageEnglish

Related product manuals