OM 1263 • MICROTECH UNIT CONTROLLER 78 www.DaikinApplied.com

ERROR CODE: E7 – Malfunction of Outdoor Unit Fan Motor
Remote
Controller
Display
E7
Method of
Malfunction
Detection
Detect a malfunction based on the current value in the INVERTER PC board (as for motor
2 current value in the fan PC board).
Detect a malfunction for the fan motor circuit based on the number of rotation detected by
hole IC during the fan motor operation.
Malfunction
Decision
Condition
Overcurrent is detected for INVERTER PC board (A2P) or fan INVERTER PC board
(A5P) (System down is caused by 4 times of detection.)
In the condition of fan motor rotation, the number of rotation is below the xed number
for more than 6 seconds. (System down is caused by 4 times of detection.)
Supposed
Causes
Failure of fan motor
Defect or connection error of the connectors/ harness between the fan motor and PC
board
The fan can not rotate due to any foreign substances entangled.
Clear condition: Continue normal operation for 5 minutes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech III DPS and is the answer not in the manual?

Daikin MicroTech III DPS Specifications

General IconGeneral
BrandDaikin
ModelMicroTech III DPS
CategoryController
LanguageEnglish

Related product manuals