OM 1263 • MICROTECH UNIT CONTROLLER 18 www.DaikinApplied.com
Unit Status Settings
The “Unit Status Settings” menu provides a summary of basic unit status and control items. This menu summarizes the current
operating state of the unit, giving the operating state the unit is in, along with the current capacity level of that operating state.
Table 3: Unit Status Settings
Item Display Name Default Setting Range Password Level
System Mode= Local
Local
6
Remote
Heat/Cool In= Heat/Cool
Heat
6
Cool
CmpIntrLock= —
Open
6
Closed
CmpCapIn= — 0-100% 6
SAFSSIn= —
O
6
On
SAFCapIn= — 0-100% 6
EAFSSIn= —
O
6
On
EAFCapIn= — 0-100% 6
RhtVlvIn= — 0-100% 6
OADCapIn= — 0-100% 6
AlmResetIn= —
Normal
6
Clear
Dehum Status= —
Inactive
6
Active
Clg Status= —
Enabled
6
NA
OAmb
OAlarm
NA
NA
Htg Status= —
Enabled
6
NAOAmb
OAlarm
NANA
Clg Capacity= — 0-100% 6
Htg Capacity= — 0-100% 6
Reheat Cap= — 0-100% 6
SAF Speed= — 0-100% 6
RF/EF Cap= — 0-100% 6
OAD/Econo Cap= — 0-100% 6