www.DaikinApplied.com 37 OM 1263 • MICROTECH UNIT CONTROLLER
 Description Values (Default in Bold)
“ROC
Applicability”
16 Return Fan Type
0=None
6=EBMVAV
7=EBMCAV
17
Return/Exhaust Fan Capacity Control
Method
0=None
1=Tracking NA
2=Building Pressure NA
3=Speed/Network NA
4=OADamper NA
18 Second Duct Pressure Sensor
0=No
NA
1=Yes
19 Entering Fan Temp Sensor
0=No
NA
1=Yes
20 Energy Recovery
0=None
1=ConstSpdWh/NoRH
2=VarSpdWhl/Danfoss
3=VarSpdWhl/MD2 NA
4=VarSpdWhl/MD3 NA
5=VarSpdWhl/ABB
6=ConstSpdWhl/wRH
21 Cooling Circuit Type
0=Individual NA
1=2,3 or 4 Circ. Water Condenser NA
2=2 Circ Air Condesner
22 Head Pressure Control
0=No
1=Yes NA
23 Bypass Valve Control
0=Slave
1=Bypass NA
24,25,26 Unit Size Three Digits (Default = 050)
27 Refrigerant Type
0=R22 NA
1=R407C NA
2=R410A
28 Reheat Type
0=None
2=ModHG
3=StdHtRht NA
29 Unit Voltage
0=208/60Hz
1=230/60Hz
2=460/60Hz
3=575/60Hz
4=208/50Hz
5=230/50Hz
6=460/50Hz
7=575/50Hz
30 Expansion Valve Type
0=None
1=EVBSag
4=MTIIIDF

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech III DPS and is the answer not in the manual?

Daikin MicroTech III DPS Specifications

General IconGeneral
BrandDaikin
ModelMicroTech III DPS
CategoryController
LanguageEnglish

Related product manuals