www.DaikinApplied.com 37 OM 1263 • MICROTECH UNIT CONTROLLER
Description Values (Default in Bold)
“ROC
Applicability”
16 Return Fan Type
0=None ●
6=EBMVAV
7=EBMCAV
17
Return/Exhaust Fan Capacity Control
Method
0=None ●
1=Tracking NA
2=Building Pressure NA
3=Speed/Network NA
4=OADamper NA
18 Second Duct Pressure Sensor
0=No
NA
1=Yes
19 Entering Fan Temp Sensor
0=No
NA
1=Yes
20 Energy Recovery
0=None ●
1=ConstSpdWh/NoRH ●
2=VarSpdWhl/Danfoss ●
3=VarSpdWhl/MD2 NA
4=VarSpdWhl/MD3 NA
5=VarSpdWhl/ABB ●
6=ConstSpdWhl/wRH ●
21 Cooling Circuit Type
0=Individual NA
1=2,3 or 4 Circ. Water Condenser NA
2=2 Circ Air Condesner ●
22 Head Pressure Control
0=No ●
1=Yes NA
23 Bypass Valve Control
0=Slave ●
1=Bypass NA
24,25,26 Unit Size Three Digits (Default = 050) ●
27 Refrigerant Type
0=R22 NA
1=R407C NA
2=R410A ●
28 Reheat Type
0=None ●
2=ModHG ●
3=StdHtRht NA
29 Unit Voltage
0=208/60Hz ●
1=230/60Hz ●
2=460/60Hz ●
3=575/60Hz ●
4=208/50Hz ●
5=230/50Hz ●
6=460/50Hz ●
7=575/50Hz ●
30 Expansion Valve Type
0=None ●
1=EVBSag ●
4=MTIIIDF ●