4 Way Valve Problem - (4WayValve: Problem)
This alarm occures only on heat pump units when any of
the following conditions are true. When compressor heating
state is normal yet the DFT-Teg > 10°F for 15 minutes. When
compressor cooling state is normal yet the DFT-Teg < or equal
to 15°F for 15 mintues. When cooling or heating state is
normal, defrost cycle is inactive, and 4 way valve ag is false
for 15 minutes. Or when compressor state transisitons from
alternate initialization to normal and 4 way valve ag is false.
When this alarm is active compressor cooling and heating
operaiton is disabled.
The alarm must be manually cleared once corrective action is
taken.
Protection Interlock Problem - (Protection
Interlock Problem)
This alarm occures when the following are true for 90 seconds:
system mode is remote, inverter compressor start/stop
command is on, and compressor interlock is o󰀨.
When this alarm is active compressor cooling and heating
operation is disabled.
The alarm must be manually cleared once corrective action is
taken.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech III DPS and is the answer not in the manual?

Daikin MicroTech III DPS Specifications

General IconGeneral
BrandDaikin
ModelMicroTech III DPS
CategoryController
LanguageEnglish

Related product manuals