ESIE16-03B | Part 5. Appendix 5.1. Field setting
Page 102 22/08/16 | Version 1.1
SA R32 Sky-Air RZAG-L
5.1.1.3. Sky-Air R32 indoor field settings
Mode No. First Code No. Description of Setting
Second Code No.
01 02 03 04 05
10 (20) 0 Filter cleaning sign interval Long life filter 2,500 hrs. (factory setting) 1,250 hrs. — — —
1 Filter type Long (factory setting) Super long — — —
2 Remote controller thermistor Enabled Disabled (factory setting) — — —
3 Filter cleaning sign Display (factory setting) No display — — —
7 (note 3) Detection time for NOT presence 30 min (factory setting) 60 min — 0,,,,0 —
8 (note 4) Compensation of suction air temperature in heating mode COMPENSATE
(Temperature [A+2] °C which an air
conditioner controls when the tem-
perature of a remote controller is A
°C) (factory setting)
NO COMPENSATION
(Temperature [A] °C which an air
conditioner controls when the tem-
perature of a remote controller is A
°C)
———
11 (21) 2 Fan OFF at Thermostat OFF Normal (factory setting) OFF — — —
3 Airflow rate setting during heating Standard (factory setting) Slightly up Up — —
4 Automatic operation mode control Available (factory setting) Prohibition — — —
6 (note 5) Sensitivity of presence sensor High Low Standard (factory setting) Sensor does not work —
11 (22) 0 Option (KRP1B*) output Compressor (factory setting) Option Operation Malfunction —
7 (note 5) Compensation of temperature around human body Floor sensor does not work Higher priority on the air tempera-
ture
Standard (factory setting) Higher priority on the floor tempera-
ture
—
8 (note 5) Compensation of floor temperature -4°C -2°C ±0°C (factory setting) +2°C —
12 (22) 3 Fan speed heating thermostat OFF LL-speed (factory setting) Set-speed — — —
5 Automatic restart after power failure reset Disabled Enabled (factory setting) — — —
6 Fan speed cooling thermostat OFF LL-speed Set-speed (factory setting) — — —
13 (23) 0 High air outlet velocity (for high ceiling applications) Standard (factory setting) Slightly up Up — —
1 Selection of airflow direction 4-way flow (factory setting) 3-way flow — — —
2 Flap moving in the swing mode All 4 flaps synchronized — Two opposite flaps synchronized
(factory setting)
——
4 Airflow range setting Upper Normal (factory setting) Lower — —
14 (24) 2 The largest time interval for Dust Collection Sign Display
for "self cleaning decoration panel"
About 1250 hrs (dusty place) About 2500 hrs (factory setting) About 5000 hrs (less dusty place) — —
4 Display or non-display of green lamp on the selfcleaning
decoration panel
Display both:
- airconditioning operation,
- filter auto cleaning
Non display:
- airconditioning operation,
Display:
- filter auto cleaning
(factory setting)
Display:
- airconditioning operation,
Non display:
- filter auto cleaning
——
8 Auto control operation for Filter Auto Cleaning Auto control operation Not auto control operation (factory
setting)
———
9 Filter cleaning time for "selfcleaning decoration panel" Normal place in terms of dust (Nor-
mal office) (factory setting)
In case of dusty place — — —
15 (25) 5 Individual setting of ventilation Normal (factory setting) Individual operation — — —
1b (2b) 14 Wind block (note 6) enable / disable setting Enable (factory setting) — — — Disable
INFORMATION
1. Settings are made simultaneously for the entire group, however, if you select the mode No. inside parentheses, you can also set by each individual unit. Setting changes however cannot be checked except in the individual mode for those in parentheses. (Even if the setting
are made for the entire group, the display always indicates “01”.)
2. “88” may be displayed to indicate the remote controller is resetting when returning to the normal mode.
3. This function does not work when “SET BACK Function” is set by remote controller.
4. This is the case when the remote sensor (optional kit) is used.
5. This is the case when the sensor option (optional kit) is used.
6. Wind block: one of 4 flaps can be set a block position (block position = closed position).
Wind can not be blocked 100% but mostly blocked without additional parts.