ESIE16-03B | Part 4. Maintenance 4.1. Indoor unit
22/08/16 | Version 1.1 Page 95
SA R32 Sky-Air RZAG-L
Part 4. Maintenance
This part contains the following chapters:
4.1. Indoor unit
4.1.1. General maintenance indoor unit
1. Optimal operation conditions
2. Correlation of air-conditioner's operation status, pressure and running current
* Water in the refrigerant freezes inside the electronic expansion valve and is basically the same phenomenon as pump down.
** Dirt in the refrigerant clogs filters inside the piping and is basically the same phenomenon as pump down.
*** Pressure differential between high and low pressure becomes low.
Indoor unit ............................................................................................................................................................................................95
Outdoor unit..........................................................................................................................................................................................96
Cooling Heating
Differential between suction temperature
and discharge temperature
8~18°C 14~30°
DB 27°C 20°C
WB 19°C NA
COOLING Low pressure High pressure Running current
Dirty air filter Lower Lower Lower
Short circuit of air inlet/outlet Lower Lower Lower
Air mixed in refrigerant Higher Higher Higher
Water mixed in refrigerant Lower* Lower Lower
Dirt mixed in refrigerant Lower** Lower Lower
Refrigerant shortage (gas) Lower Lower Lower
Unsatisfactory compression Higher*** Lower Lower