ESIE16-03B | Part 5. Appendix 5.2. Detailed information setting mode
SA R32 Sky-Air RZAG-L
22/08/16 | Version 1.1 Page 109
5.2.3.2. I-Demand Function
Set a limitation towards the power consumption from the system (e.g. budget control, limit power consumption during peak moments, ...).
3 different demand setting can be selected by using terminal X801M:
• Demand 1 → Close contact between COM and contact 1
• Demand 2 → Close contact between COM and contact 2
• Demand 3 → Close contact between COM and contact 3
Demand 1
Power consumption limitation in function of setting on DS1.
Demand 2
Power consumption limitation set to 40%.
Demand 3
Forced thermostat OFF.
5.2.3.3. Setting for Low Humidity Application
Can be set when using the RZAG-L units for year round cooling in low humidity applications such as computer rooms (EDP rooms), technical rooms, etc...to increase the capacity of the unit.
Model RZQG71 RZQG100 RZQG125 RZQG140
Sound reduction 6 dBA 5 dBA 6 dBA 7 dBA
DS1 Setting
Maximum Power
Consumption
1 2
OFF OFF 60%
ON OFF 70%
OFF ON 80%
ON ON 100%