ESIE16-03B | Part 3. Repair 3.3. Unit specific repair procedures
22/08/16 | Version 1.1 Page 71
SA R32 Sky-Air RZAG-L
3.3.2.2. Replacing thermistor
Removal
1. Switch off the Daikin unit via the user interface.
2. Switch off the Daikin unit with the field supplied circuit breaker.
3. Remove plate work when required (refer to "Basic removal" on page 67).
Figure 3-9: Thermistor location
Thermistor Processed on PCB Connector / colour
R1T (air) Main X11A
R2T (discharge) Main X12A / yellow
R3T (suction) Main X12A / green
R4T (heat exchanger) Main X12A / red
R5T (heat exchanger middle) Main X12A / white
R6T (liquid) Main X13A: / blue
R7T, R8T (Positive Temperature Coefficient) - -
1. R1T 4. R4T
2. R2T 5. R5T
3. R3T 6. R6T
2
5
3
1
5
3
1
4
6
2
4
6