ESIE16-03B | Part 2. Troubleshooting 2.4. Component checklist
Page 56 22/08/16 | Version 1.1
SA R32 Sky-Air RZAG-L
15. Power the Daikin unit.
16. Activate the inverter test (refer to "Component checklist" on page 121).
17. Check that all LED’s on the Inverter Analyzer are lit; if not, replace the inverter board (refer to "Replacing inverter PCB" on
page 87).
18. Switch off the Daikin unit with the field supplied circuit breaker.
19. Wait a few minutes and confirm that the LED's on the Inverter Analyzer are off.
20. Disconnect the Inverter Analyzer from the U V W wiring.
21. Reconnect the U V W leads to the compressor.
WARNING
Electrical shock hazard. Do not touch life wires.
CAUTION
When wiring the compressor, observe UV W as indicated on the compressor.