EasyManua.ls Logo

Daikin SV1A25AJV1B - To Perform a SV Unit Test Run

Daikin SV1A25AJV1B
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 | Commissioning
Installer and user reference guide
113
SV1A25AJV1B+SV4~8A14AJV1B
VRV 5 safety valve unit
4P749917-1 – 2023.09
About measuring with a hot wire probe anemometer
Attention: In case you need to drill holes in the ducting, choose a location
without thermal insulation.
Where: Measure the airflow rate in the duct connected to the air outlet of the SV
unit.
Postrequisite: Close the holes properly once the measurement is finished.
a
d
b
c
a SV unit
b Air outlet duct
c Direction airflow
d Hot wire probe anemometer
18.3.4 To perform a SV unit test run
See "17.1.8 Mode 2: field settings" [4 104] for more information on the settings
that are used.
Respect the sequence indicated in "18.3.1About the SV unit test run"[4110]. Do
not perform a test run on more than one SV unit at a time.
Prerequisite: All refrigerant piping work is finished.
1 Change field setting [2‑3] to "1". This setting simulates a refrigerant leak and
activates the safety measures according to the field settings that have been
made. See "18.3.1 About the SV unit test run" [4 110] to check which units
need a setting change.
2 In case of a configuration with an external alarm, check that the external
alarm warns both audibly (15dBA above the sound of the surroundings) and
visibly.
3 In case of a configuration with a ventilated enclosure, measure the airflow
rate. See "18.3.3 About measuring the airflow rate" [4 112] for more
information.
4 In all configurations, check if no safety measures are activated that are not
intended to activate.
5 Change field setting [2‑3] to "0". This setting deactivates the test run.
6 Change field setting [2‑6] to "1" for all SV units of the system, even those
where the test run was not activated (e.g. downstream SV units in a ventilated
enclosure series configuration). This setting confirms that the safety measures
are working correctly and - in the case of ventilated enclosure it confirms
that the extraction airflow rate complies to the legal limits.

Table of Contents

Other manuals for Daikin SV1A25AJV1B

Related product manuals