16 | Electrical installation
Installer and user reference guide
93
SV1A25AJV1B+SV4~8A14AJV1B
VRV 5 safety valve unit
4P749917-1 – 2023.09
Terminal Wiring Screw size Tightening
torque (N•m)
Earth screw Earth wiring M4 1.52~1.86
X2M~X5M Transmission wiring M3.5 0.79~0.97
X6M External output
16.2 To connect the electrical wiring
NOTICE
Follow the wiring diagram (delivered with the unit, located at the inside of the
service cover).
For instructions on how to connect the optional equipment, see the installation
manual delivered with the optional equipment.
Make sure the electrical wiring does NOT obstruct proper reattachment of the
service cover.
1 Remove the service cover. See "14.3.1To open the unit"[468].
2 Strip insulation from the wires.
a b
a Strip wire end to this point
b Excessive strip length may cause electrical shock or leakage
Allowed
Not allowed
3 Connect the interconnection wiring as follows:
Connection for SV4A~SV8A
Connect the terminals F1/F2 (TO IN/D) on the control PCB in the outdoor
unit's switch box to the terminals F1/F2 (Outdoor unit) on terminal block
X2M of the first SV unit. See also the installation manual delivered with the
outdoor unit.
In case of multiple SV units in the system that are connected to the same
interconnection wiring branch line, connect the terminals F1/F2 (SV unit) on
terminal block X2M of the first SV unit to the terminals F1/F2 (Outdoor unit)
on terminal block X2M on the second SV unit. Repeat the same procedure
for further SV units, where each time the terminals F1/F2 (SV unit) on
terminal block X2M on the n
th
SV unit are connected to the terminals F1/F2
(Outdoor unit) on terminal block X2M on the (n+1)
th
SV unit.