EasyManua.ls Logo

Daikin SV1A25AJV1B - Preparing Refrigerant Piping; Refrigerant Piping Requirements; Refrigerant Piping Material; Refrigerant Piping Insulation

Daikin SV1A25AJV1B
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15 | Piping installation
Installer and user reference guide
83
SV1A25AJV1B+SV4~8A14AJV1B
VRV 5 safety valve unit
4P749917-1 – 2023.09
15.2 Preparing refrigerant piping
15.2.1 Refrigerant piping requirements
NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use
phosphoric acid deoxidised seamless copper for refrigerant piping.
INFORMATION
Also read the precautions and requirements in the "2 General safety
precautions"[47].
Foreign materials inside pipes (including oils for fabrication) must be
≤30mg/10m.
15.2.2 Refrigerant piping material
Piping material: phosphoric acid deoxidised seamless copper
Piping temper grade and thickness:
Outer diameter (Ø) Temper grade Thickness (t)
(a)
6.4mm (1/4")
9.5mm (3/8")
12.7mm (1/2")
Annealed (O) ≥0.80mm
t
Ø
15.9mm (5/8") Annealed (O) ≥0.99mm
19.1mm (3/4")
22.2mm (7/8")
Half hard (1/2H) ≥0.80mm
28.6mm (11/8") Half hard (1/2H) ≥0.99mm
(a)
Depending on the applicable legislation and the maximum working pressure of the unit (as
indicated on the unit nameplate), larger piping thickness might be required.
15.2.3 Refrigerant piping insulation
Use polyethylene foam as insulation material:
- with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045kcal/mh°C)
- with a heat resistance of at least 120°C
Insulation thickness:
Ambient temperature Humidity Minimum thickness
≤30°C 75% to 80% RH 15mm
>30°C ≥80% RH 20mm