16 | Electrical installation
Installer and user reference guide
98
SV1A25AJV1B+SV4~8A14AJV1B
VRV 5 safety valve unit
4P749917-1 – 2023.09
Note: When joining branch pipe ports, ONLY the combinations in above table are
possible. E.g.: it is NOT possible to join ports B and C.
Example When joining branch pipe ports A and B.
Examples
1. When connecting an indoor unit to branch pipe ports A, B,
and D, but NOT connecting an indoor unit to branch pipe
portC.
2. When joining branch pipe ports A and B. Connecting an
indoor unit to the joined branch pipe ports A and B, also to
branch pipe portC, but NOT connecting an indoor unit to
branch pipe portD.
ON
DS1 (A1P)
OFF
1 2 3 4
ON
DS2 (A1P)
OFF
1 2 3 4
16.5 To connect the external outputs
FAN output (extraction fan)
The extraction FAN output is a contact on terminal X6M that closes in case a leak is
detected, or when there is a failure or disconnection of the R32 sensor in the SV
unit.
The FAN output must be used when a ventilated enclosure is required (see
"13.3To determine the required safety measures"[445]).
a FAN output terminals (1 and 2)
b Cable to extraction fan circuit
Select and dimension the wiring in accordance with the applicable legislation based
on the information in the notice below:
NOTICE
The FAN output has a limited capacity of 220~240VAC – 0.5A.
Do NOT use the FAN output to directly power the fan. Instead, use the output to
energise a relay that controls the fan circuit.
a FAN output terminal
b Relay
c Extraction fan power supply