13 | Special requirements for R32 units
Installer and user reference guide
62
SV1A25AJV1B+SV4~8A14AJV1B
VRV 5 safety valve unit
4P749917-1 – 2023.09
(a)
Set on ALL main PCBs (A1P and A2P) of the SV unit.
(b)
Set ONLY on the LEFTMOST main PCB (A1P) of the SV unit.
SV units (e) with natural ventilation
Code Description Value
[2-0]
(a)
Cluster indication 0 (default): disable
[2-4]
(b)
Safety measures 0: disable
[2-7]
(b)
Ventilated enclosure 1 (default): enable
(a)
Set on ALL main PCBs (A1P and A2P) of the SV unit.
(b)
Set ONLY on the LEFTMOST main PCB (A1P) of the SV unit.
Note: For more information, see "17.1Making field settings"[4100].
SV unit test run
Before SV unit operation, it is required to perform a test run that simulates a
refrigerant leak. See "18.3SV unit test run"[4110] for more details.